ZW32-40.5(35)KV series Outdoor Reclosing Vacuum Circuit Breaker,Integrated with isolation switch

Quick details:
Brand Name: HOSSIN
Model Number: ZW32
Usage: Indoor/Outdoor
Voltage level: 33-40.5kV
Safety Standards: IEC
Place of production: China-Zhejiang
Export Markets: Global
Packing: wooden-box or as customized

product description

The ZW32-40.5 series outdoor miniaturized vacuum circuit breaker is mainly composed of integrated solid-sealed poles, current transformers, operating mechanisms, and boxes. An isolation switch can be installed. This model of circuit breaker is miniaturized in design, and its casing is made of a high-quality steel box. Current transformers can be selected according to user needs.

This device is mainly used in medium-voltage overhead line power grids to divide and combine load current, overload current, and short-circuit current.

normal usage conditions

● Ambient temperature: not higher than +40℃, not lower than -15℃; relative air humidity: daily average value is not greater than 95%, monthly average value is not greater than 90%;

●The altitude does not exceed 1500 meters; The earthquake intensity does not exceed level 8;

●No place with fire, explosion, serious pollution, chemical corrosion and severe vibration. Note: If customers have other special requirements, they can put them forward when ordering, and our company will provide maximum satisfaction.

Model meaning

Main technical parameters

project unit parameter
Rated voltage kV 40.5(35)
Rated current A 630/1250
Rated frequency Hz 50 or 60
The industrial frequency resistance is 1min (wet) (dry) (dry), the opposite/fracture kV 81
Lightning impact tolerance current (peak) phase, opposite/fracture kV 185
The rated short -circuit open current kA 20/25/31.5
The rated short -circuit level -off current (peak value) kA 63/80
The rated peak tolerance current kA 63/80
4S short -term tolerance current kA 25/31.5
Rating operation cycle NaN Society -0.1S-Section-3S-Points-6S Points-60S recovery
The number of short -circuit currents at the rated short circuit Second-rate 30
Mechanical life Second-rate 10000
Institutional control voltage V AC/DC220
Two circuit LMIN industrial frequency resistance kV 2
Touches mm 18±1
Ultra -stroke mm 4±0.5
Splitting speed m/s 1.4-1.8
Closing speed m/s 0.4-0.8
Jumping time ms ≤5
Central distance mm 560±2
What periods are different in three phases ms ≤2
Direction circuit resistance of each phase μΩ < 80
Time ms ≤100
Splitting time ms ≤50
weight KG No isolation 300 Isolation 380

Overall dimensions

Scroll to Top