YH10W-42 42kV Lightning Arrester

The HY series composite sheathed lightning arrester is the basis for the insulation coordination of various electrical equipment in the power system (such as transformers, reactors, capacitors, generators, motors, PT, CT, circuit breakers, contactors, etc.).

Technical Performance

The technical performance of metal-oxide surge arresters is in accordance with IEC 60099-4 and IEEE (ANSI) C62.11.

Structural Design

The module core design was developed in the early 80s and has over 15 years of service experience, with the housing material changing in the early 90s.

The modular single-column polymer housing metal-oxide surge arrester design is available for up to 220 kV systems.

The essential feature of the internal patented construction is the permanent homogenous resin and fiberglass bond over the complete insulating service of the metal-oxide varistor. The arrester module has an inherently high mechanical strength and provides a uniform dielectric at the insulating surface of the metal-oxide varistor.

Advantage 

Low residual voltage

Long protection distance

high energy input capacity

Stable U-I characteristics even after multiple strokes

Proof against ageing

Explosion- and shatter-resistant design

Pollution-resistant and UV-stable

housing resistant to rough handling

stable against shock and vibration

High mechanical resistance

Metal-oxide Surge Arrester (YH10W-42kV)

Technical Details:

1. Applicable Standard IEC60099-4

2. Rated Voltage (Ur): 42 kV

3. Max. Continuous Operating Voltage (Uc): 34 kV

4. Nominal Discharge Current: 10 kA

5. Max. Residual Voltage Corresponding To

a) steep current impulse (145 kVp)

b) lightning impulse leval A1 Nominal Discharge Current: 126 kVp

c) Switching Current Impulse Level: 107 kVp

6. 2ms ms Current current withstand: 250A

7. 4/10us Impulse Withstand:100kA

Scroll to Top