HY10WZ-108/280W Composite jacket, Zinc Oxide Aarrester

Quick details:
Brand Name: HOSSIN
Model Number: HY5W/HY10W
Usage: Indoor/Outdoor
Voltage level: 108kV
Safety Standards: IEC
Place of production: China-Zhejiang
Export Markets: Global
Packing: wooden-box or as customized

Product Introduction

HY10WZ-108/281 Zinc Oxide Arrester is used to protect AC electrical equipment in power plants and substations from damage from atmospheric overvoltage and operating voltage. Lightning arrester is a device that protects equipment in substations from lightning shock waves. When the lightning shock wave introduced into the substation along the line exceeds the protection level of the arrester, the arrester will discharge, and the lightning current will be safely introduced into the ground through a good conductor. The grounding device is used to limit the amplitude of the lightning voltage to the lightning shock level of the protected equipment. Keep electrical equipment protected.

HY10WZ-108/281 Zinc Oxide Arrester can be divided into: protection gap, a simpler form of arrester; tubular arrester, – is also a protection gap, but it can extinguish the arc by itself after discharge; and valve arrester, which is a single discharge arrester. The gap is divided into many short series gaps, and at the same time, non-linear resistance is added to improve the protection performance; magnetic blowing arrester: using the magnetic blowing spark gap, the arc extinguishing ability is improved, and it also has the ability to limit internal overvoltage; zinc oxide Surge arrester: utilizes the ideal volt-ampere characteristics of zinc oxide valve plates (high nonlinearity, that is, low resistance characteristics at large currents, limiting the voltage on the arrester, and high resistance characteristics under normal power frequency voltage), with The advantages of no gap, no freewheeling, and low residual voltage can also limit the internal overvoltage and are widely used.

Model Description

Working Environment:

  1. Suitable for indoor and outdoor;
  2. Ambient temperature: -40℃~+40℃;
  3. The altitude should not exceed 3000m (the porcelain sleeve type should not exceed 1000m);
  4. The frequency of the power supply is not less than 48Hz and not more than 62 Hz.
  5. The power frequency voltage applied between the arrester terminals for a long time does not exceed the continuous operating voltage of the arrester;
  6. Areas with an earthquake intensity of 8 degrees and below;
  7. The maximum wind speed should not exceed 35 m/s.

Overall dimensions:

Main technical parameters

Model No. system rated voltage arrester rated voltage continuous operating voltage DC reference voltage (U1mA) steep wave impulse current residual voltage lightning impulse current residual voltage residual pressure under operating impulse current square wave flow capacity (2ms) high current impulse withstand
kV(r.m.s) kV >kV A kA
HY5WZ-5/13.5 3 5 4.0 7.5 15.5 13.5 11.5 150 65
HY5WZ-10/27 6 10 8.0 15.0 31.0 27 23.0 150 65
HY5WZ-17/45 10 17 13.6 24.0 51.5 45 38.3 150 65
HY5WZ-51/134 35 51 40.8 73.0 154 134 114 400 100
HY5WZ-54/134 35 54 43.2 77.0 154 134 114 400 100
HY5WZ-84/221 66 84 67.2 121 254 221 188 600 100
HY5WZ-90/235 66 90 72.5 130 270 235 201 600 100
HY5WZ-100/260 110 100 78.0 145 299 260 221 600 100
Scroll to Top