FN18(NAL)-24D 24KV LBS load break switch indoor air

FN18(NAL)-24D 24KV LBS load break switch indoor air

FN18(NAL) series Load break switch, the air insulated type switch disconnectors (Load Break Switches) of NAL and NALF areintended for indoor installation in air-insulated switchgear systems.
Category: Switchgear & High Voltage Products
Brand: Hossin electric power
Model: FN18-24D(NAL)
Power: 24KV/ 630A
FOB Port: Ningbo/Shanghai

Product Description

FN18(NAL) series Load break switch, the air insulated type switch disconnectors (Load Break Switches) of FN18(NAL) and NALF areintended for indoor installation in air-insulated switchgear systems.

FN18-DR is a general purpose, three-pole, load break switch that offers switchgear owners and assemblers the advantages of an advanced interrupting technology and proven, dependable performance in a compact design. The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear applications in ratings from 12-40.5 kV. The standard FN18 switch includes a heavy-duty steel frame with stand-off insulators, a unique puffer-type arc extinguishing system, an operating mechanism and current-carrying components, including blade-type interrupters with cast hinges and jaw connectors. Optional accessories and features include a variety of operating handles, a motor operator, auxiliary switches, a shunt trip device, fuse bases, mechanical fuse tripping, grounding switches, mechanical door interlocking and key interlocking.

Introduction

The LBS type NAL/NALF is based on a modular principle. The basic unit consists of a framewith insulators and current carrying parts. Two different types of operating mechanisms.snap action mechanism type K or stored spring energy mechanism type A, can be mounted onthe frame. Fuse bases type F, with or without fuse tripping mechanism, and an earthing switchtype E/EB, suitable for both direct mounting and free standing components, complete thebasic equipment of a switch disconnector. These modules can be easily configured accordingto customer expectations. Accessories, such as shunt trip, under-voltage release, auxiliaryswitches, motor operation and various systems for manual operation can easily be added.

Product features

A NAL Load Break Switch (which interrupts load currents up to 1,250 A) and a small fault-current circuit combined with a fuse base (F) and current limiting fuses (which break largeshort-circuit currents) create a NALF-type Load Break Switch that provides protection againstamajority of fault types in a modern electric network.
Operating conditions

Ambient temperature:

Maximum +40ºC Maximum 24 hour average +35ºC
Minimum (according to “minus 5 indoorclass”)-15ºC·
Humidity: Daily average ambient air relative humidity ≤ 95%, on average ≤ 90%;
Saturated vapor pressure of daily mean values s 2.2 x 10-3Mpa, on averages 1.8 x10- 3Mpa;
Maximum site altitude:≤ 1000 M above sea level,

FN18 (NAL/NALF)

Model

FN18/NAL/NALF-12

FN18/NAL/NALF-24

Rated Voltage

12KV

24KV

Rated Frequency

50/60Hz

50/60Hz

Rated Current

630A

630A

Rated Short Circuit Closing Current

67KA

50KA

Rated Peak Withstand Current (Dynamic Steady Current)

67KA

50KA

Rated Short-Time Withstand Current(Thermally Stable Current)

1s

31.5KA

25KA

2s

25KA

25KA

3s

20KA

16KA

Max. breaking capcity in co-operation with fuse

1600A

900A

Max.fuse current

200A

200A

1 min Power Frequency Withstand Voltage(Effective Value)Ground and Phase

to earth and between poles

42KV

65KV

across isolating distance

48KV

79KV

Lightning Impulse Withstand Voltage(Peak) 1.2/50 μs

to earth and between poles

75KV

125KV

across isolating distance

85KV

145KV

Product size