FL(R)N48-12D/630-20 indoor sulfur hexafluoride load switch

Quick details:
Brand Name: HOSSIN
Model Number: FLN48-12
Usage: Indoor
Voltage level: 11-40.5kV
Safety Standards: IEC
Place of production: China-Zhejiang
Export Markets: Global
Packing: wooden-box or as customized

product description

The FL(R)N48 series indoor high-voltage sulfur hexafluoride load switch and its fuse combination electrical appliances are developed and designed by our company by absorbing advanced foreign technology and combining it with my country’s actual operating requirements. This product complies with IEC62271, IEC60265, IEC60420, GB3804, GB16926, and other standard requirements. This product has three stations of “opening-closing-grounding” and is reliably interlocked. Install a cable head type load switch, with a touchable cable front connector installed at the outlet end, and high-voltage cables installed at the incoming and outgoing lines, which are installed in the cable branch box. The switch’s special dynamic seal and fixed seal design ensure reliable sealing, and a pressure gauge is installed at an obvious location for monitoring during operation to ensure safe operation. This product is suitable for three-phase AC (12 kV, 50/60 Hz) power systems.

Product Technical Parameters

FL (R) N48 technical parameters
Rated voltage kV 12
Rated current A 630
Rated frequency Hz 50/60
The rated short-circuit level combination current (peak) ka 62.5
The rated peak tolerance current (peak) kA 62.5
Short-time tolerance current (effective value)1 second kA 25
The maximum opening of the break current (when the fuse is used) IEC 62271-105 (IEC 420 1990-11) A 1530
Main valid load current A 630
Cable charging current A 630
The rated short-time work frequency tolerance voltage 50Hz 1 min,:
-Mhande kV 42
-The disconnect kV 45
The rated lightning shock tolerance voltage 1.2/50 μs
-Mhande kV 75
-The disconnect kV 85
Mechanical life cycles 3000

Dimensional drawing