FKW18-40.5 Outdoor air arc extinguishing switch,Rotate horizontally

Quick details:
Brand Name: HOSSIN
Model Number: FKW18
Usage: Indoor/Outdoor
Voltage level: 11-40.5 kV
Safety Standards: IEC
Place of production: China-Zhejiang
Export Markets: Global
Packing: wooden-box or as customized

Overview and purpose

The FKW18-40.5/630-20 outdoor AC high-voltage isolation load switch (hereinafter referred to as the load switch) is a comprehensive domestic existing load switch. New load switches are designed and manufactured with mature production experience and advanced foreign technology. The load switch is composed of an isolation blade, an arc extinguishing chamber, and an operating mechanism. Adopting the principle of gas generation and arc extinguishing, it has the characteristics of a simple structure and low maintenance. It has the advantages of less protection, strong arc extinguishing ability, high fracture insulation level, and high reliability, reaching the advanced level of similar foreign products. This load switch is suitable for outdoor three-phase AC power distribution systems with a rated voltage of 40.5 kV and below and a rated frequency of 50 Hz. It can be used to break and close distribution lines, and it can also be used to break and close no-load lines and no-load transformers. In the opening position, it can meet the requirements of isolated power requirements specified by isolating switches.

Use environmental conditions

a) Ambient air temperature: upper limit +40℃, lower limit -25℃, daily temperature difference does not exceed 32K; b) Altitude: 1000m; c) Wind pressure does not exceed 700Pa (equivalent to wind speed 34m/s); d) Air pollution level: Level IV according to Article 4.1 of GB5582; e) The seismic intensity does not exceed 8 degrees; f) The thickness of the ice shall not exceed 10m.

Product model and name

Main technical parameters

Serial number project unit parameter
1 Rated voltage kV 40.5
2 Rated current A 630
3 Rated frequency Hz 50
4 The rated peak tolerance current kA 50
5 The rated short-term tolerance current kA 20
6 The duration of the current short-term tolerance s 4
7 The rated contribution load opens the current A 630
8 The rated closed-loop open current A 630
9 Rating cable charging open current A 10
10 5% rated contribution load open-breaking current A 31.5
11 Air load transformer current opens to break the rated capacity kVA 1250
12 The rated short -circuit level combined current kA 50
13 Master circuit resistance μΩ ≤95
14 1min industrial frequency tolerance voltage (valid value) Between poles, poles to ground (dry test/wet test) kV 95/115
polar, pole to the ground 85
15 Lightning impulse withstand voltage (peak value) polar, pole to the ground kV 185
isolation break opening 215
16 Mechanical life times 2000
17 Three phases and gates of the same period ms ≤15
18 Motor voltage, power VW ≌220 ≤200
19 The touch of the knife is just sloping mm ≤5
20 Main touch knife pressure N 420±42
21 Touches mm >=360
22 Rated operating torque N.m >=3

Overall dimensions and installation diagram

Ordering instructions

Please specify when ordering:

a) Product model, name, quantity;

b) Environmental conditions of use;

c) Installation method;

d) Name and quantity of spare products and spare parts;

e) If there are other special requirements, they should be negotiated with the manufacturer.