BHA-10/400 (630) -20 Russia Indoor high voltage Load break switches U2 isolators switch with fuse grounding disconnected

Quick details:
Brand Name: HOSSIN
Model Number: BHA
Usage: Indoor
Voltage level: 10 kV
Safety Standards: IEC
Place of production: China-Zhejiang
Export Markets: Global
Packing: wooden-box or as customized

Purpose of the devices

The BHA type Load break switches are designed to turn on and off sections of the three-phase alternating current circuit 400 and 630 A with a frequency of 50-60 Hz, rated voltage up to 10 kV, under load, as well as to ensure safe work on the disconnected section using stationary earthing devices. The PRBD-10 drive is designed for manual operation of the switch.

Environmental Conditions

·         Suitable Altitude: 1000m ~ 4000m

·         Suitable Temperature: -40℃ ~ +45℃

·         Relative Humidity: Daily mean ≤95%, monthly mean ≤90%

·         No conductivity dust.

·         No insulation object with devastating metal and corrosive gas.

·         No violent vibration or striking.

·         No explosive danger or fire.

 Technical Data

Name Unit Date
Rated Voltage K V 12
Rated Frequency Hz 50
Rated Current A 400 630
Rated Short-Time Withstand Current (Thermally Stable Current) K V 12.5(4s) 20(2s)
Rated Peak Withstand Current (Dynamic Steady Current) K A 31.5 50
Rated Closed-Loop Breaking Current A 400 630
Rated Active Load Breaking Current A 400 630
5% Rated Active Load Breaking Current A 20 31.5
Rated Cable Charging Breaking Current A 10
Rated Breaking No-Load Transformer Capacity 1250
Rated Short Circuit Closing Current K A 31.5 50
Load Current Breaking Times Times 20(100% Load) 35(60% Load) 75(30% Load) 80(5% Load)
1 min. Power Frequency Withstand Voltage (Effective Value) K V 42 Ground and Phase
Power Frequency Withstand Voltage (Between Isolation Gaps) K V 48
Lightning Impulse Withstand Voltage (Peak) K V Ground and Phase 75, Isolation Fracture 85
Opening and Closing Operation Torque (Force) N.m(N) 90(180) 100(200)