FXB1-15KV/70KN Power Line Electrical Composite Polymer Insulator 24KV36KV

Dimension drawing

Fxb-15/70 Power Line Electrical Composite Polymer Insulator
Type Rated voltage Rated mechanical load Spacing Dry arcing distance Creepage distance Power frequency wet with stand voltage Dry lightning impulse withstand voltage
FXB-15/70 15kV 70kN 380mm 195mm 460mm 65kV 140kV
FXB-24/70 24kV 70kN 455mm 260mm 680mm 70kV 155kV

Product Defect

(1) The price of composite insulators is high.

(2) Composite insulators bear a very small radial (perpendicular to the center line) stress; therefore, the use of high-voltage insulators used in tension rods or any form of radial load is strictly prohibited; otherwise, it will lead to breaking.

(3) When the composite insulator is in construction or normal operation, it is strictly prohibited to drop and rub hard objects. Because the umbrella part is silicone rubber, the texture is relatively tender, and it is easy to damage and destroy the sealing, resulting in a decline in insulation performance.

The Product Installation

Installation of composite insulator

1.1 check

Before the installation of composite insulators, the insulators shall be inspected one by one according to GB/P5892. Insulators with a torn sheath, damaged sheath, or damaged end seal shall not be used.

1.2 Precautions for composite insulators

A) Handle with care, do not throw, and avoid collision and friction with sharp objects;

B) When lifting, the rope knot should be tied to the metal accessory, and it is forbidden to tie it directly to the umbrella cover. When the rope touches the umbrella cover, it should be wrapped in a soft cloth for protection

C) It is prohibited to step on the insulator umbrella cover;

D) Install the pressure equalizing device correctly, pay attention to the installation in place, do not install reverse, and carefully adjust the torus

Perpendicular to the axis of the insulator. For opening

Type 6 pressure equalizing device; note that both ends open in the same direction.