Overview and purpose
The FKW18-40.5/630-20 outdoor AC high-voltage isolation load switch (hereinafter referred to as the load switch) is a comprehensive domestic existing load switch. New load switches are designed and manufactured with mature production experience and advanced foreign technology. The load switch is composed of an isolation blade, an arc extinguishing chamber, and an operating mechanism. Adopting the principle of gas generation and arc extinguishing, it has the characteristics of a simple structure and low maintenance. It has the advantages of less protection, strong arc extinguishing ability, high fracture insulation level, and high reliability, reaching the advanced level of similar foreign products. This load switch is suitable for outdoor three-phase AC power distribution systems with a rated voltage of 40.5 kV and below and a rated frequency of 50 Hz. It can be used to break and close distribution lines, and it can also be used to break and close no-load lines and no-load transformers. In the opening position, it can meet the requirements of isolated power requirements specified by isolating switches.
Use environmental conditions
a) Ambient air temperature: upper limit +40℃, lower limit -25℃, daily temperature difference does not exceed 32K; b) Altitude: 1000m; c) Wind pressure does not exceed 700Pa (equivalent to wind speed 34m/s); d) Air pollution level: Level IV according to Article 4.1 of GB5582; e) The seismic intensity does not exceed 8 degrees; f) The thickness of the ice shall not exceed 10m.
Product model and name
Main technical parameters
Serial number | project | unit | parameter | |
---|---|---|---|---|
1 | Rated voltage | kV | 40.5 | |
2 | Rated current | A | 630 | |
3 | Rated frequency | Hz | 50 | |
4 | The rated peak tolerance current | kA | 50 | |
5 | The rated short-term tolerance current | kA | 20 | |
6 | The duration of the current short-term tolerance | s | 4 | |
7 | The rated contribution load opens the current | A | 630 | |
8 | The rated closed-loop open current | A | 630 | |
9 | Rating cable charging open current | A | 10 | |
10 | 5% rated contribution load open-breaking current | A | 31.5 | |
11 | Air load transformer current opens to break the rated capacity | kVA | 1250 | |
12 | The rated short -circuit level combined current | kA | 50 | |
13 | Master circuit resistance | μΩ | ≤95 | |
14 | 1min industrial frequency tolerance voltage (valid value) | Between poles, poles to ground (dry test/wet test) | kV | 95/115 |
polar, pole to the ground | 85 | |||
15 | Lightning impulse withstand voltage (peak value) | polar, pole to the ground | kV | 185 |
isolation break opening | 215 | |||
16 | Mechanical life | times | 2000 | |
17 | Three phases and gates of the same period | ms | ≤15 | |
18 | Motor voltage, power | VW | ≌220 ≤200 | |
19 | The touch of the knife is just sloping | mm | ≤5 | |
20 | Main touch knife pressure | N | 420±42 | |
21 | Touches | mm | >=360 | |
22 | Rated operating torque | N.m | >=3 |
Overall dimensions and installation diagram
Ordering instructions
Please specify when ordering:
a) Product model, name, quantity;
b) Environmental conditions of use;
c) Installation method;
d) Name and quantity of spare products and spare parts;
e) If there are other special requirements, they should be negotiated with the manufacturer.