Y10WZ-100/260,Y10W-108/280Zinc Oxide Arrester Porcelain Insulation

Quick details:
Brand Name: HOSSIN
Model Number:Y10W
Usage: Indoor/Outdoor
Voltage level: 72-145 kV
Safety Standards: IEC
Place of production: China-Zhejiang
Export Markets: Global
Packing: wooden-box or as customized

Product Introduction

The Y10WZ-108/280 Porcelain Jacket Arrester is an arrester with good protective properties. Using the good nonlinear volt-ampere characteristics of zinc oxide, the current flowing through the arrester is extremely small (microamp or milliamp level) under normal working voltage; when overvoltage acts, the resistance drops sharply, discharging the energy of the overvoltage and achieving a protective effect. The difference between this arrester and the traditional arrester is that it has no discharge gap and uses the nonlinear characteristics of zinc oxide to play the role of leakage and interruption.

Y10WZ-108/280 Porcelain JAcket Arrester is the current international advanced overvoltage protector. Because its core element resistor is made of zinc oxide and various metal oxides, compared with the traditional silicon carbide arrester, the volt-ampere characteristics of the resistor are greatly improved, and the current capacity of the resistor is improved, thereby improving the characteristics of the arrester. fundamental change.

When the arrester is under normal operating voltage, the current flowing through the arrester is only microampere. When subjected to overvoltage, the excellent nonlinear volt-ampere characteristics of the arrester play a role, and the current flowing through the arrester instantly increases to thousands of amperes. In the conduction state, the overvoltage energy is released, thereby effectively limiting the damage of the overvoltage to the power transmission and transformation equipment.

Model Description

Working Environment:

  1. The ambient temperature is not higher than +40 °C. Not lower than -40°C;
  2. Altitude: no more than 2000m;
  3. Power frequency: 50/60Hz;
  4. Earthquake intensity: 7 degrees and below;
  5. Maximum wind speed: 35 m/s;
  6. No cleaning conditions: moderately dirty and below areas;
  7. For gapless products, the long-term applied power frequency voltage shall not exceed the continuous operating voltage of the arrester;
  8. For products with gaps, the short-term power frequency voltage rise at the installation point shall not exceed the rated voltage of the arrester.

For long-term use in the following abnormal conditions, the arrester needs to be specially made and should be specified when ordering:

  • The temperature or altitude exceeds the standard (plateau, tropical, frigid, fully enclosed cabinet, close to electric furnace, etc.);
  • There are serious moisture or corrosive gas impurities in the environment (water, salt fields, chemical plants, etc.);
  • Strong ultraviolet radiation (plateau, strong sunshine area, etc.);
  • Extraordinarily polluted areas (mine face, construction site face, etc.).

Main Technical Parameters

Arrester model Y10WZ-100/260 Y10WZ-102/266 Y10WZ-108/281
Arrester rated voltage (kV) RMS 100 102 108
System nominal voltage (kV) RMS 110 110 100
Continuous operating voltage (kV) RMS 78 79.6 84
DC 1mA reference voltage (kV) not less than 145 148 157
Maximum residual voltage kV (RMS) Under lightning impulse current 1.3 2.6 3.9
Under steep impulse current 291 297 315
Under lightning impulse current 260 266 281
operating under inrush current 221 226 239
2000μs square wave flow capacity (A) 600
4/10 high current withstand capability (kA) 100
Maximum leakage current (μA) at 0.75 times DC reference voltage 50
Creepage distance (mm) 3150

Reference Size